Safety Manual. Revised Edition 2010

Revised Edition 2010

Risk Assessment: Electromechanical Erection

Workers Affected by Works Hazards

PREVENTIVE MEASURES

Rules for acting

  • Qualified/Authorised Workers (Spanish Royal Decree 614/01): Work with an electrical hazard must be carried out and/or supervised by the qualified/authorised workers deemed proper, in accordance with the stipulations of Spanish Royal Decree 614/01 and in ISASTUR procedures (see PC0712 and the corresponding Technical Instructions):
SUMMARY CHART FOR MINIMUM STAFF TRAINING/QUALIFICATIONS
NON-VOLTAGE WORK LIVE WORK MANOEUVRES, MEASUREMENTS, TESTS AND CHECKS PROXIMITY WORK
Suppressing and reconnecting the power supply Carrying out of non-voltage work Execution Replacing fuses Measurements, tests and checks Local manoeuvres Preparation Execution
Low voltage A W Q A A A A T
High voltage Q W Q+AW (overseen by a Foreman) Q
(remote)
Q o Q
(aided by A)
A Q A o W
(overseen by A)
W= Any worker. A = Authorised worker.
Q= Qualified worker.
Q+AW= Qualified and authorised in writing.
1. HV work with electrical hazards cannot be carried out by workers from a Temporary Work Company (Spanish Royal Decree 216/1999).
2. The carrying out of the different activities considered is to be done in accordance with the stipulations of the present Spanish Royal Decree.
LIMIT DISTANCES FOR WORK AREAS
Un DPEL-1 DPEL-2 DPROX-1 DPROX-2
≤1 50 50 70 300
3 62 52 112 300
6 62 53 112 300
10 65 55 115 300
15 66 57 116 300
20 72 60 122 300
30 82 66 132 300
45 98 73 148 300
66 120 85 170 300
110 160 100 210 500
132 180 110 330 300
220 260 160 410 300
380 390 250 540 700
Un rated voltage of the installation (kV).
DPEL-1 distance to the outer limit of the danger zone when there is a risk of overvoltage caused by lightning (cm)
DPEL-2 distance to the outer limit of the danger zone when there is no risk of overvoltage caused by lightning (cm).
DPROX-1 distance to the outer limit of the proximity zone when it is possible to precisely demarcate the work area and to establish controls that impede anyone from going beyond this limit during the carrying out of such work (cm).
DPROX-2 distance to the outer limit of the proximity zone when it is not possible to precisely demarcate the work area or to establish controls that impede anyone from going beyond this limit during the carrying out of such work (cm).
The distances for intermediate voltage values are to be calculated by linear interpolation.