Work on Electrical Installations and in premises presenting a fire or explosion hazard

Definitions and concepts:

17. Non-Voltage Work – EXCEPTIONS

All work on an electrical installation or in its vicinity that entails an electrical hazard is to be carried out with the power supply off, except:

  • Basic operations: connection and disconnection in LV installations, with suitable electrical material and without any risk to the public.
  • Work on installations under safety voltage, when there exists no risk of confusion (complex installations) or burns (the installations conveys high currents).
  • Manoeuvres, measurements, tests and checks that so require it: opening/closing of switches or circuit-breakers, measurement of current, insulation tests, checking phase concordance.
  • Work on or in the vicinity of installations whose conditions of exploitation/continuity so require it. For instance: requirements to comply with Quality and Continuity Regulations (Spanish Royal Decree 1955/2000); the cut-off of supply supposes risks for the health and safety of the population or of a group of persons within said population.

18. Table of limit distances for work areas

TABLE OF LIMIT DISTANCES FOR WORK AREAS
Vr DDAN-1 DDAN-2 DPROX-1 DPROX-2
≤ 1 50 50 70 300
3 62 52 112 300
6 62 53 112 300
10 65 55 115 300
15 66 57 116 300
20 72 60 122 300
30 82 66 132 300
45 98 73 148 300
66 120 85 170 300
110 160 100 210 500
132 180 110 330 500
220 260 160 410 500
380 390 250 540 700
Vr = rated voltage of the installation in (kV).
DDAN-1= distance to the outer limit of the danger zone when there is a risk of overvoltage caused by lightning (cm).
DDAN-2= distance to the outer limit of the danger zone when there is no risk of overvoltage caused by lightning (cm).
DPROX-1= distance to the outer limit of the proximity zone when it is possible to precisely demarcate the work area and to establish controls that impede workers from going beyond this limit during the carrying out of such work (cm).
DPROX-2= distance to the outer limit of the proximity zone when it is not possible to precisely demarcate the work area or to establish controls that impede anyone from going beyond this limit during the carrying out of such work (cm).
(Note): For intermediate voltage values, the distances corresponding to the voltage value that figures in the table and which is immediately superior to the actual voltage value are to be considered.

19. Table of limit distances for work areas

SUMMARY CHART FOR MINIMUM STAFF TRAINING/QUALIFICATIONS
  Non-voltage work Live work Manoeuvres, measurements, tests and checks Proximity work
Supression and reconnection of voltage Non-voltage work Carrying out of Replacing fuses Measurements, tests and checks Local manoeuvres Preparation of Carrying out of
Low Voltage A T C A A A A T
High Voltage C T C+AE
(supervised by a Foreman)
C C o C
assisted by A
A C A o T
supervised by A
T= Any worker
A= Authorised worker
C= Qualified worker
C+AE= Qualified and authorised in writing
1. HV work with electrical hazards cannot be carried out by workers from a Temporary Work Company (Spanish Royal Decree 216/1999).
2. The carrying out of the different activities considered is to be done in accordance with the stipulations of the present Spanish Royal Decree.